Why Traditional HVAC Systems Fail to Control Humidity
- Summer Neal

- Feb 2
- 4 min read
Humidity control is one of the most misunderstood challenges in industrial and commercial buildings. Many facilities assume that if an HVAC system is properly sized for temperature, humidity will “take care of itself.” In reality, temperature control and humidity control are related, but not the same thing.
Temperature Control Is Not Humidity Control
Conventional HVAC systems are designed first and foremost to manage sensible heat—that is, air temperature. Moisture removal (latent heat) is essentially a secondary function.
In a typical cooling cycle, air passes over a cold evaporator coil. If the coil surface temperature is below the air’s dew point, moisture condenses and drains away. This process works reasonably well when cooling loads are high and outdoor conditions are hot and humid.
The problem is that industrial facilities rarely operate under “ideal” conditions for coil-based dehumidification.
The Key Limitation
HVAC systems can only remove moisture when they are actively cooling. When sensible loads drop but latent loads remain, humidity control suffers.
The Sensible–Latent Load Mismatch
Many industrial environments have low or variable sensible loads but high latent loads. Examples include:
Food and beverage processing
Pharmaceutical manufacturing
Cold storage and refrigerated spaces
Warehouses with frequent door openings
Facilities with washdown processes
Indoor pools or water treatment plants
In these spaces, moisture enters the building through:
Ventilation air
Infiltration from doors and loading docks
Process-related evaporation
Occupants and equipment
When the HVAC system cycles off because the space temperature is satisfied, moisture removal stops—even though humidity continues to rise.
This is the classic sensible–latent imbalance, and it is the primary reason traditional HVAC systems fail at humidity control.
Overcooling and Reheat: An Inefficient Workaround
One common attempt to solve humidity issues with conventional HVAC is overcooling followed by reheat.
Here’s how it works:
The air is cooled well below the space temperature to remove enough moisture.
The air is then reheated to avoid overcooling the space.
While this method can reduce humidity, it introduces several problems:
High energy consumption (cooling and heating at the same time)
Increased mechanical complexity
Higher operating costs
Reduced sustainability and efficiency metrics
In many regions, energy codes and corporate sustainability goals actively discourage or prohibit this approach.
Coil Limitations in Industrial Environments
Even when HVAC systems are designed to dehumidify, cooling coils themselves impose physical limitations.
Coil Temperature Constraints
To remove moisture, coil surfaces must operate below the air’s dew point. However:
Extremely cold coils increase the risk of freezing
Low airflow rates reduce heat transfer efficiency
Frost buildup further degrades performance
Part-Load Conditions
Most facilities operate at part load the majority of the time. At part load:
Compressors cycle off more frequently
Coil temperatures rise
Moisture removal becomes inconsistent
The result is wide humidity swings that are unacceptable for many industrial processes.
Ventilation Air: The Hidden Moisture Load
Ventilation air is one of the largest sources of moisture in commercial and industrial buildings—especially in humid climates.
Outdoor air often enters the system at:
High humidity ratios
High dew points
Conditions far above acceptable indoor moisture levels
Cooling-based HVAC systems must lower this air below its dew point to remove moisture. When outdoor humidity is extreme, this becomes impractical or inefficient.
In contrast, desiccant dehumidifiers are designed specifically to handle high moisture loads, regardless of temperature.
Why Desiccant Dehumidification Works Where HVAC Fails
Desiccant dehumidifiers remove moisture through adsorption, not condensation. A hygroscopic material (the desiccant) attracts and holds water vapor directly from the air.
This fundamental difference creates several advantages.
Independent Control of Temperature and Humidity
Desiccant systems decouple latent and sensible control. Moisture can be removed:
Without overcooling the air
Without relying on low coil temperatures
Across a wide range of operating conditions
This allows engineers to design systems that precisely meet humidity requirements while allowing HVAC systems to focus on temperature.
Low Dew Point Capability
Many industrial processes require very low dew points—often well below what cooling coils can achieve economically. Desiccant systems can consistently deliver:
Low humidity ratios
Stable dew points
Year-round performance
Reliable Performance at Part Load
Unlike HVAC systems, desiccant dehumidifiers do not rely on compressor cycling to remove moisture. They provide:
Continuous moisture removal
Stable humidity control
Predictable performance during light load conditions
Industrial Risks of Poor Humidity Control
For engineers and facility managers, the consequences of uncontrolled humidity are not theoretical—they’re operational and financial.
Common issues include:
Corrosion of equipment and infrastructure
Mold and microbial growth
Product spoilage or contamination
Condensation on ceilings, ductwork, and piping
Slippery floors and safety hazards
Regulatory compliance failures
Sales teams often find that customers are already experiencing these problems—they just don’t realize humidity is the root cause.
A Complementary, Not Competitive, Solution
It’s important to note that desiccant dehumidifiers are not a replacement for HVAC systems. Instead, they complement traditional HVAC by addressing what HVAC was never optimized to do.
A well-designed system often includes:
HVAC equipment sized for sensible cooling
Desiccant dehumidification sized for latent load
Improved energy efficiency
Better process control
Longer equipment life
For engineers, this approach offers better system stability and design flexibility. For sales professionals, it provides a clear, technically sound value proposition.
Conclusion
Traditional HVAC systems fail to control humidity not because they are poorly designed—but because they were never designed to prioritize latent load control in demanding industrial environments.
When humidity matters—and in many industrial spaces it absolutely does—cooling-based systems alone are not enough. Desiccant dehumidification provides the independent, reliable, and energy-efficient moisture control that modern facilities require.
Understanding this distinction empowers engineers to design better systems and enables sales professionals to have more informed, credible conversations with customers. In the end, controlling humidity isn’t about adding more cooling—it’s about using the right technology for the job.




Comments